48--BLRI - REPLACE DEFECTIVE 8' PIV VALVE
Overview
Buyer
Place of Performance
NAICS
PSC
Set Aside
Original Source
Timeline
Qualification Details
Fit reasons
- NAICS alignment with historical contract wins in similar service areas.
- Scope strongly matches core technical capabilities and delivery model.
Risks
- Past performance thresholds may require one additional teaming partner.
- Potential clarification needed on staffing minimums before bid/no-bid.
Next steps
Validate eligibility requirements, assign capture owner, and schedule partner outreach to confirm teaming strategy before submission planning.
Quick Summary
The National Park Service (NPS), specifically the SER NORTH MABO (53000) office, is soliciting proposals for the replacement of a defective 8-foot Post Indicator Valve (PIV) at the Vinton Maintenance Facility on the Blue Ridge Parkway. This is a Total Small Business Set-Aside. The project requires the contractor to provide all necessary supervision, labor, equipment, testing, and supplies. Proposals are due by January 27, 2026, at 1500 EST.
Scope of Work
The contractor will be responsible for the complete removal and replacement of a defective 8-foot PIV on the fire suppression system at 2551 Mountain View Rd, Vinton, VA 24179. Key tasks include:
- Scheduling a site assessment and utility survey with Roanoke County, VA.
- Performing Lockout/Tagout (LOTO) on the water system.
- Removing and disposing of the existing PIV and associated piping.
- Providing and installing a new 8-foot PIV and associated piping, ensuring it is an 8-inch barrel or valve body. The PIV is installed underground and uses a telescoping indicator.
- Reconnecting the system, restoring water pressure, and verifying no leaks.
- Confirming proper system water pressure.
- Excavation and backfill are required, with utility surveys coordinated.
- Filling, grading, and leveling all disturbed areas, followed by seeding with a specified BLRI grass seed mix.
- Cleaning up the work area and verifying the operation of the new PIV.
Key Requirements
All work and materials must be new, compatible with the existing system, and approved by the Contracting Officer's Representative (COR). Compliance with NFPA 13 and NFPA 25 standards is mandatory. Qualified personnel experienced in commercial fire protection system inspection, maintenance, and valve replacement are required. OSHA guidelines for underground work must be followed. The contractor must furnish all necessary supervision, personnel, equipment, transportation, materials, and incidentals. A minimum 1-year warranty against defects and a 5-year warranty for workmanship are required.
Contract Details
- Contract Type: Solicitation for commercial items.
- Set-Aside: Total Small Business Set-Aside (FAR 19.5). Only small business concerns will be considered.
- NAICS Code: 238220, with a size standard of $19 million.
- Period of Performance: February 2, 2026, to April 4, 2026.
- Place of Performance: 2551 Mountain View Rd, Vinton, VA 24179. Work hours are Monday through Friday, 7 AM - 4:30 PM.
Submission & Evaluation
Technical acceptability will be evaluated on a Pass/Fail basis; failure to meet any requirement will result in ineligibility. Price will be evaluated for fairness and reasonableness. The Government intends to award without discussions but reserves the right to conduct them. Required submittals include Contractor Liability Insurance and Warranty Information. Closeout submittals include a binder with manufacturer product information and cut-sheets.
Important Dates & Contacts
- Proposal Due Date: January 27, 2026, at 1500 EST.
- Site Visit: Scheduled for January 22, 2026. Interested offerors must email jordan_hatfield@nps.gov to coordinate attendance.
- Primary Contact: Arcoiris Cuetara-Higa (arcoiris_cuetara-higa@nps.gov).
Additional Notes
This solicitation includes a U.S. Department of Labor Wage Determination (No. 2015-4369, Rev. 29) for the Service Contract Act, applicable to North Carolina counties (Buncombe, Henderson, Madison). Bidders must incorporate these minimum wage rates and fringe benefits into their proposals. Technical specifications for the AMERICAN AVK TELESCOPIC INDICATOR POST, model 34/0X, are provided, detailing compatibility, materials, and approvals, which are crucial for understanding the specific PIV requirements.